rubber sheathed flexible cable

YC, YCW general rubber sheathed flexible cable

YC, YCW general rubber sheathed flexible cable Manufacturing standard:Gb5013.4-1997 jb8735.2-1998, the standard adopted by this product is consistent with iec245 (1994) of International Electrotechnical Commission. Product application: This product is applicable to household appliances, electric tools and various mobile multi electrical equipment with AC rated voltage of 450 / 750V and below. The long-term working temperature of the cable should not exceed 65 ℃ “W” type cable has weather resistance and certain oil resistance,Suitable for outdoor oil contact. Cable type

Model Name purpose
YC, YCW Heavy rubber sheathed flexible cable It is used in all kinds of mobile electrical equipment and can bear large mechanical external force

Anhui Tiankang (Group)Shares Co., Ltd
YC, YCW general rubber sheathed flexible cable Technical performance of cable structure:   
    When the insulation resistance between cable insulation cores is converted to the temperature of 20 ℃ 35mm, it shall be:2And below50m Ω· km 50-150 mm not less than2And below30m Ω· km 185-240mm not less than2And below20m Ω· km 435mm not less than nominal section2Cables of the following specifications shall be able to withstand the bending test. After 1500 times of reciprocating bending test, the sample shall be free of current breaking, and shall be able to withstand the voltage test of ycycwc50hz 2500v5min at AC 50Hz 2000v5min.The structure and resistance of the conductive cores of the cables which shall undergo the AC voltage test  rubber cable

Nominal section mm2 structure 20 ℃ conductor DC resistance Ω / km Nominal section mm2 structure 20 ℃ conductor DC resistance Ω / km
0.3 16/0.15 Less than 69.2 16 126/0.40 Less than 1.21
0.5 28/0.15 Less than 39 25 196/0.40 Less than 0.780
0.75 24/0.20 Less than 26 35 276/0.40 Less than 0.554
1.0 32/0.20 Less than 19.5 50 396/0.40 Less than 0.386
1.5 30/0.25 Less than 13.3 70 360/0.50 Less than 0.272
2.5 49/0.25 Less than 7.98 95 475/0.50 Less than 0.206
4 56/0.30 Less than 4.95 120 608/0.50 Less than 0.161
6 84/0.30 Less than 3.30 150 756/0.50 Less than 0.129
10 84/0.40 Less than 1.91      

450/750V YC YCWHeavy rubber sheathed flexible cable

Core number × standard number section mm Average outer diameter mm Calculated weight of cable kg / km 20The resistance Ω / km at centigrade is not more than Allowable carrying capacity of air laying
lower limit Upper limit YC YCW Copper core Tin plated copper core
1 x 1.5 5.6 7.2 55 57.0 13.3 13.7 20
1 x 2.5 6.4 8.0 73.7 79.5 7.98 8.21 27
1 x 4 7.2 9.0 110.5 118.7 4.95 5.09 36
1 x 6 8.0 11.0 135 167.3 3.30 3.39 47
1 x 10 9.8 13.0 220.6 234.8 1.91 1.95 65
1 x 16 11.0 14.5 295.1 311.6 1.21 1.24 85
1 x 25 12.5 16.5 425.6 446.2 0.780 1.79 115
1 x 35 14.0 18.5 561.9 587.5 0.554 0.565 145
1 x 50 16.5 21.0 758.4 788.4 0.386 0.393 175
1 x 70 18.5 4.0 1034.1 1073.7 0.272 0.277 220
1 x 90 21.0 26.0 1324.7 1369.3 0.206 0.210 265
1 x 120 23.0 28.5 1598.9 1646.3 0.161 0.164 310
1 x 150 25.0 32.0 1974.6 2108 0.129 0.132 360
1 x 185 27.5 34.5 2540 2498 0.106 0.108 410
2 x 1.5 9.0 11.5 132 146.6 13.3 13.7 16
2 x 2.5 10.5 13.5 203.6 223.9 7.98 8.21 23
2 x 4 12.0 15.0 280.2 305.6 4.95 5.09 30
2 x 6 13.5 18.0 412.2 448.20 3.30 3.39 39
2 x 10 18.5 24.0 669.1 732.8 1.91 1.95 55
2 x 16 21.0 27.5 906.6 988.5 1.21 1.24 73
2 x 25 24.5 31.5 1144.3 1321 0.780 0.795 96
3 x 1.5 9.6 12.5 164 1890 13.3 13.7 14

Heat Trace Cable

Core number × standard number section mm Average outer diameter mm Calculated weight of cable kg / km 20The conducting resistance Ω /km is not more than Allowable carrying capacity of air laying
lower limit Upper limit YC YCW Copper core Tin plated copper core
5 x 10 4.0 31.0 1205.2 1289.0 1.91 1.95 40
5 x 16 27.0 35.5 1668.8 1777.0 1.21 1.24 53
5 x 25 32.5 41.5 2434.3 2578.1 0.780 0.795 70

3+1core

Core number × standard number

Section mm

Average outer diameter mm Calculated weight of cable kg / km 20The resistance Ω / km at centigrade is not more than Allowable carrying capacity of air laying
lower limit Upper limit YC YCW Copper core Tin plated copper core
3 x 1.5+1 x 1 9.4 12.0 13.3 13.7 14
3×2.5+1×1.5 11.0 14.0 282.7 305.6 7.98 8.21 19
3 x 4+1 x 2.5 13.0 16.0 406.8 435.7 4.95 5.09 26
3 x 6+1 x 4 14.5 19.5 600.1 640.34 3.30 3.39 33
3 x 10+1 x 6 20.5 26.5 925.1 990.9 1.91 1.95 47
3 x 16+1 x 6 23.0 26.5 1253.9 1341.5 1.91 1.95 62
3 x 16+1 x 10 23.0 30.0 1.21 1.24 63
3 x 25+1 x 10 28 35.5 1823.2 1941.5 0.780 0.795 83
3 x 35+1 x 10 30.0 38.5 1980.4 244.7 0.554 0.565 100
3 x 50+1 x 16 36.0 46.0 3952 3439.7 0.368 0.393 125
3 x 70+1 x 25 40.0 51.0 4504.4 4772.6 0.272 0.277
3 x 95+1 x 35 46.5 59.0 5972 6346 0.206 0.210
3 x 120+1 x 35 46.5 59.0 6362.1 6662.4 0.161 0.164
3 x 150+1 x 50 52.0 66.0 7889.3 8252.6 0.129 0.132

 3+2core

Core number × standard number section mm Average outer diameter mm Calculated weight of cable kg / km 20The resistance Ω / km at centigrade is not more than Allowable carrying capacity of air laying
lower limit Upper limit YC YCW Copper core Tin plated copper core
3 x 4+2 x 2.5 14.3 17.8 399 415 4.95 5.09 26
3 x 6+2 x 4 19.5 23.0 607 631 3.30 3.39 33
3 x 10+2 x 6 23.0 26.0 914 947 1.91 1.95 47
3 x 16+2 x 6 28.5 33.5 1194 1235 1.21 1.24 62
3 x 25+2 x 10 30.0 35.0 1697 1762 0.780 0.795 83
3 x 35+ x 10 36.0 41.0 2275 2350 0.554 0.565 100
3 x 50+2 x 16 40.0 45.0 3074 3117 0.386 0.393 125
3 x 50+2 x 25 42.5 45.5 3454 3564      
3 x 70+2 x 25 44.0 50.0 4165 4285 0.272 0.272
3 x 95+2 x 35 46.0 52.5 5552 5270 0.206 0.10
3 x 120+2 x 35 52.0 58.0 6405 6550 0.161 0.164
3 x 150+2 x 50 61.0 67.0 8065 8376 0.129 0.132
3 x 185+2 x 50 78.0 86.0 9538 9891 0.106 0.108
3 x 240+2 x 70 81.0 89.0 12083 12580 0.0801 0.0817
3 x 150+2 x 70 62.5 66.0 8224 8394      

 4+1core

Core number × standard number section mm Average outer diameter mm Calculated weight of cable kg / km 20The resistance Ω / km at centigrade is not more than Allowable carrying capacity of air laying
lower limit Upper limit YC YCW Copper core Tin plated copper core
4 x 4+1 x 2.5 14.5 17.0 411 427 4.95 509 24
4 x 6+1 x 4 19.5 22.0 626 651 3.30 3.93 30
4 x 10+1 x 4 24 26.5 1081 1125 1.91 1.95 43
4 x 25+1 x 10 29.5 33.0 1983 2050 0.780 0.795 71
4 x 35+1 x 10 36.4 39.9 2582 2675 0.554 0.565 98
4 x 50+1 x 25 38.5 43.5 3525 3635 0.386 0.393 115
4 x 70+1 x 25 49.0 54.0 4730 4950 0.272 0.277 140
4 x 95+1 x 35 56.0 61.0 6353 6550 0.206 0.210 170
4 x 120+1 x 35 60.0 65.0 7674 7891 0.161 0.204 195
4 x 150+1 x 50 69.0 74.5 9375 9650 0.129 0.132 220
4 x 185+1 x 50 82.0 87.5 11367 11845 0.106 0.108
4 x 240+1 x 70 85.0 91 14151 14659 0.0801 0.0817